| Sign In | Join Free | My insurersguide.com |
|
Model Number : 080G0310 / MCX08M2
Supply Voltage : 24 VAC / 24 VDC
Packaging Details : Anti-static Bag + Carton Box + Foam Protection
Brand Name : Danfoss
Controller Type : Programmable HVAC/R Controller
Supply Ability : 10 Units per Month
Payment Terms : T/T
Application : Chillers; AHU; Heat Pumps; Refrigeration
Price : USD 1089 - 1269 / Unit
Attribute Name Attribute Value Controller Type Programmable HVAC/R Controller Supply Voltage 24 VAC : CANbus; Modbus RS485
Place of Origin : Denmark
Relay Outputs : 8 Relay Outputs
MOQ : 1 unit
Display : Integrated LED Display
The Danfoss 080G0310 MCX08M2 is an eight-relay programmable controller for medium-sized and complex HVAC/R applications. It combines expanded input/output capacity, an integrated graphic LCD, CANbus communication, Modbus RS485 and a real-time clock in an eight-DIN-module housing.
The controller operates from 24 VAC or 24 VDC and provides eight analog inputs, eight digital inputs, four analog outputs and eight relay outputs. It is suitable for applications requiring more control points than the compact MCX06C or MCX06D platforms.
| Brand | Danfoss |
| Commercial Reference | 080G0310 |
| Controller Type | MCX08M2 |
| Function | Programmable HVAC/R Controller |
| AC Supply Voltage | 24 VAC |
| DC Supply Voltage | 24 VDC |
| Frequency | 50/60 Hz |
| Maximum Power Consumption | 10 W |
| Analog Inputs | 8 |
| Digital Inputs | 8 |
| Analog Outputs | 4 |
| Digital Outputs | 8 Relay Outputs |
| Display | Integrated Graphic LCD |
| Communication | CANbus; Modbus RS485 |
| Real-Time Clock | Included |
| Mounting | DIN Rail |
| Controller Width | 8 DIN Modules |
| Front Enclosure Rating | IP40 |
| Packing Format | Single Pack |
| Quantity per Pack | 1 Piece |
The MCX08M2 can be programmed for chillers, air-handling units, rooftop equipment, heat pumps, refrigeration systems, hot-water control and other applications requiring multiple temperature, pressure, status and relay-control points.
The reference 080G0310 identifies the 24 V version with an integrated LCD, RS485 and real-time clock. Other MCX08M2 references may use 110–230 VAC, omit the display, include TTL communication or be supplied in industrial packs.
Confirm the complete 080G reference, power supply, display, communication, product version, BIOS and installed application before replacement. A blank MCX08M2 controller requires compatible application software and machine-specific parameter commissioning.
Related models include 080G0293 MCX08M2 24 V without integrated LCD, 080G0307 MCX08M2 110–230 V with LCD, 080G0315 industrial-pack equivalent and 080G0335 MCX08M2 with TTL communication.
Please provide the complete reference 080G0310, original controller nameplate, machine model and software information when requesting a quotation. Confirm whether the controller must be supplied with application programming or as hardware only.
|
|
Danfoss 080G0310 MCX08M2 Programmable HVAC/R Controlle Images |